Heat Island Effect: Roof
LEED 2.2 Requirements:
OPTION 1
Use roofing materials having a Solar Reflectance Index (SRI)* equal to or greater than the values in the table below for a minimum of 75% of the roof surface.
OPTION 2
Install a vegetated roof for at least 50% of the roof area.
OPTION 3
Install high albedo and vegetated roof surfaces that, in combination, meet the following criteria:
- (Area of SRI Roof / 0.75) + (Area of vegetated roof / 0.5) >= Total Roof Area
- For a Low-Sloped Roof with Slope = 2:12, the SRI = 78
- For a Steep-Sloped Roof with Slope > 2:12, the SRI = 29
*The Solar Reflectance Index (SRI) is a measure of the constructed surface's ability to reflect solar heat, as shown by a small temperature rise. It is defined so that a standard black (reflectance 0.05, emittance 0.90) is 0 and a standard white (reflectance 0.80, emittance 0.90) is 100. To calculate the SRI for a given material, obtain the reflectance value and emittance value for the material. SRI is calculated according to ASTM E 1980. Reflectance is measured according to ASTM E 903, ASTM E 1918, or ASTM C 1549. Emittance is measured according to ASTM E 408 or ASTM C 1371.
Submittals (DESIGN):
Provide copies of the project's roof drawings to highlight the location of location and quantity of specific roofing materials and/or vegetated roofing systems, as applicable. In addition, please provide the following based on the appropriate compliance path:
Option 1 - Roofing Materials with SRI equal to or greater than required
- Provide total area (sf) of installed low-sloped roofing materials having a minimum SRI of 78.
- Provide total area (sf) of installed steep-sloped roofing materials having a minimum SRI of 29.
- Indicate the SRI Value for each installed roofing material by completing the fields in the Roofing Materials Table in the Template.
Option 2 - Vegetated Roof
- Total area (sf) of installed vegetated roofing system.
Option 3 - Combo of Roofing Materials with SRI and Vegetated Roof
- Total area (sf) of installed vegetated roofing system.
- Provide total area (sf) of installed low-sloped roofing materials having a minimum SRI of 78.
- Provide total area (sf) of installed steep-sloped roofing materials having a minimum SRI of 29.
- Indicate the SRI Value for each installed roofing material by completing the fields in the Roofing Materials Table in the Template.
- AND (For Projects With Special Circumstances - Any Compliance Path) - Provide an optional narrative to describe any additional comments or notes regarding special circumstances or considerations regarding the project's credit approach.
|